40NB Side Mount Multiport Valve filter & Softner

PP Pleated and glass fiber cartridges are designed for higher filtration area & high throughput. It has a 6 inch/152mm large diameter and is a coreless, single open-ended structure with an inside to outside flow pattern. Due to its large diameter with a big filter area, it requires lesser elements for a given flow rate than standard cartridges diameter, due to lesser elements Filter vessels’ size workout smaller, resulting in lower capital investment and installation costs, as well as reduced operating costs.

Filters :
  • Down flow Pressure Sand Filters.
  • Down flow Multi grade Filters.
  • Down flow Activated Carbon Filter.
  • Down flow Iron Removal Filter.
Procedure For Filter :
  • Shut off pump motor.
  • Press down on valve handle, rotate valve from FILTER to BACKWASH position.
  • Watch pressure gauge for back-pressure and pipe line for kinks. Be prepared to shut off pump quickly.
  • After hose fills with water, run for 2 to 3 minutes or until water runs clear.
  • Shut off pump motor and move multiport valve handle to RINSE position. Run on rinse for 5 to 10 seconds. Shut off pump again, and move handle back to BACKWASH. Turn on pump again until water runs clear. Continue in this fashion 3 to 4 times, alternating between backwash and rinse, to ensure a thorough backwash.
  • Shut off pump motor and move multiport valve handle to FILTER position.
  • Turn pump back on and note lower pressure.
Procedure For Softener :
  • Always press the handle down before turning the handle to the desired position viz. Service, Regeneration or Rinse.
  • If the line pressure is more, it is advisable to close the inlet valve before turning handle.
  • Ensure that minimum 2kg/cm2 pressure is available for getting optimum ejector performance.
  • If there is a suction problem even at 2kg/cm2 then the ejector filter screen may be clogged with dirt etc. For cleaning this, the bolts connecting the upper and lower housing of MPV have to be removed, after disconnecting/closing the inlet. Then remove the filter and wash and clean it and refit reassemble the MPV.
Valve 1.5" Filter and Softener Top Mount 1.5” filter and Softener Side Mount
Material Nylon Nylon
Media Fuel, Water Fuel, Water
Valve connection with top opening vessel 65 mm (2 ½ ") NPSM (8 tpi) or 100mm (4") -
Riser pipe size 32 mm PVC pipe -
Max. flow rate (valve + strainers) 12 m3/h 12 m3/h
Working Pressure 0.15 – 0.6 MPa 0.15 – 0.6 MPa
Working Temperature 5 – 50 °C 5 – 50 °C
Inlet, outlet, drain connections 40 mm BSPF quick release union straight 40 mm BSPF quick release union straight
Maximum Operating Pressure 4 to 6 Kg/cm2 for GF 4 to 6 Kg/cm2 for GF
Minimum pressure for uniform suction 2.0 kg/cm2 2.0 kg/cm2
Ejector brine line 1/2" BSP 1/2" BSP

Note : Riser pipe length with bottom strainer attached should be 40 mm above vessel top.

Application :
  • For Sand / Carbon / Multimedia Filter